FGD FlameSpec UV/IR-HD Flame detector

The FlameSpec-UV-IR-HD flame detector provides ultra-fast response, high performance and reliable detection of a large variety of fires including hydrocarbon fires (visible and nonvisible), as well as Hydrogen fires. ​The detector addresses slow growing fires as well as fast eruptions of fire using improved UV/IR technology. The detector operates in all weather and light conditions. In addition, the detector provides high-definition (HD) video output of the monitored area with clear imaging of a fire event and of personnel at distances up to 100 ft (30m). This allows the rescue team to be aware of the exact situation before entering the hazardous area. The detector automatically records video of any fire event (1 minute pre- and up to 3 minutes post alarm initiation). These features, along with the built-in event logger, provide additional means to study the cause and development of fire events for “lessons learned” reviews.

Characters and Benefits

  • Hydrogen and Hydrocarbons flame detection
  • Ultra-fast detection mode – detection within 5 milliseconds for fireballs or explosions
  • High sensitivity – up to 100ft (30m) for a 1ft² (0.1m²) n-heptane pan fire
  • High immunity to false alarm
  • Data/Event logger – alarms, faults and other relevant events are logged to non-volatile memory.
  • Ethernet communication – in addition to standard methods, such as 4-20mA and Modbus
  • Built-in-Test (BIT) – Automatic and manual internal self-test of window cleanliness and the overall operation of the detetor (for both IR and UV channels)
  • Window heater to avoid condensation and icing
  • Configurable detection mode – allows configuration of UV-IR, UV or IR detection modes.

Specification

Category Item Description
Fire Detection Detection time and distance 5ms for fast fire burst or explosion
1.5s for 1 ft2 (0.1m2) pan fire at 0–50 ft. (0–15m)
<3s for 1 ft2 (0.1m2) pan fire at 50–100 ft. (15–30m)
Sensitivity Range 4 Sensitivity ranges: Extreme, High, Medium, Low
Field of View (IR detection) 90° Horizontal, 80° Vertical
Time Delay 0-30 seconds
Built in Test Automatic and Manual
Electrical Specifications Operating Voltage 24 VDC nominal (18-32 VDC)
Current Consumption Standby: 180mA
Maximum: 300mA(including window heater)
Conduit Entries 2x cable and conduit entries 3/4″ NPT(F) or M25x1.5
Wiring 12-20AWG (2.5-0.35mm2)
Outputs Relays SPST volt-free contacts rated 2A at 30 VDC
Alarm – normally open; Fault – normally closed
0-20mA (stepped) current output 3 wire and 4 wire configurations (sink and source)
HART® rev 7.0 (option available)
Indication Tri-color LED (Green, Yellow, Red)
Modbus RTU compatible on RS-485
Digital (for video) IP network IEEE 802.3 100Base-T
Composite video NTSC or PAL
Mechanical Specifications Size 7.87 x 5.12 x 5.12" (200x130x130mm)
Weight Detector (Stainless Steel 316): 9.8 lbs. (4.4 kg)
Tilt mount (Stainless Steel 316): 5.4 lbs. (2.4 kg)
Environmental Specifications Temperature Range Operating: -67°F to +185°F (-55°C to +85°C)
Storage: -67°F to +185°F (-55°C to +85°C)
Humidity Up to 99% (RH), non-condensing
Ingress Protection IP66 & 68(2m, 24hr); NEMA 4X & 6P
Approvals ATEX ATEX : II 2 G D
Ex db IIC T5 Gb or Ex db eb IIC T5 Gb and Ex tb IIIC T95°C Db
-55°C < Ta < 75°C
Ex db IIC T4 Gb or Ex db eb IIC T4 Gb and Ex tb IIIC T105°C Db
-55°C < Ta < 85°C
IECEx&PESO Ex db IIC T5 Gb or Ex db eb IIC T5 Gb
and Ex tb IIIC T95°C Db -55°C<Ta<75°C
Ex db IIC T4 Gb
or Ex db eb IIC T4 Gb
and Ex tb IIIC T105°C Db -55°C<Ta<85°C
FMus & FMc Class I, Div. 1, Groups B, C & D; T4 -50°C≤Ta≤85°C or T5 -50° C≤Ta≤75°C Class II/III, Div. 1, Groups E, F, G; T4 -50°C≤Ta≤85°C or T5 -50°C≤Ta≤75°C Class I, Zone 1, AEx/Ex db IIC T4 Gb or Class I, Zone 1, AEx/Ex db eb IIC T4 Gb -50°C≤Ta≤85°C Class I, Zone 1, AEx/Ex db IIC T5 Gb or Class I, Zone 1, AEx/Ex db eb IIC T5 Gb -50°C≤Ta≤75°C Zone 21, AEx/Ex tb IIIC T95°C Db -50°C≤Ta≤75°C or Zone 21, AEx/Ex tb IIIC T105°C Db -50°C≤Ta≤85°C
EAC CU TR 1Ex d IIC T5 Gb o r 1Ex de IIC T5 Gb and Ex tb IIIC T95°C Db -55°C≤Ta≤75°C
1Ex d IIC T4 Gb or 1Ex de IIC T4 Gb and Ex tb IIIC T105°C Db -55°C≤Ta≤85°C
Performance ANSI FM 3260
EN 54-10
Functional safety Complies to SIL2, per IEC 61508 (option available)
Accesories Stainless steel weather cover, model FLS-WCO-S02
Flame simulator, model FLS-FSIM-UV-IR-KIT
2" & 3" pole mount adapters, model FLS-PMA-S23
Airshield for areas with high airborne contamination, model FLS-ASD-S02
Paint shield / cover
Warranty 5 years